http://repositorio.unb.br/handle/10482/48812
Título : | Influence of lossy ground on high-frequency induced voltages on aboveground pipelines by nearby overhead transmission lines |
Autor : | Britto, Amauri Gutierrez Martins Papadopoulos, Theofilos A. Datsios, Zacharias G. Chrysochos, Andreas I. Papagiannis, Grigoris K. |
metadata.dc.identifier.orcid: | https://orcid.org/0000-0002-2691-9061 https://orcid.org/0000-0002-8534-785X https://orcid.org/0000-0002-5259-7043 https://orcid.org/0000-0002-5712-3859 https://orcid.org/0000-0002-9470-8573 |
metadata.dc.contributor.affiliation: | University of Brasília, Faculty of Technology, Department of Electrical Engineering LAPSE University of Thrace, Power Systems Laboratory Department of Electrical and Computer Engineering Democritus, Xanthi, Greece Aristotle University of Thessaloniki, High Voltage Laboratory School of Electrical & Computer Engineering, Thessaloniki, Greece Cablel Hellenic Cables Group, Athens, Greece School of Electrical and Computer Engineering, Aristotle University of Thessaloniki, Thessaloniki, Greece |
Assunto:: | Interferência eletromagnética Linhas de transmissão Impedância Condutividade elétrica |
Fecha de publicación : | 20-sep-2022 |
Editorial : | IEEE |
Citación : | BRITTO, Amauri Gutierrez Martins et al. Influence of lossy ground on high-frequency induced voltages on aboveground pipelines by nearby overhead transmission lines. IEEE Transactions on Electromagnetic Compatibility, [S. l.], v. 64, n. 6, 2273 - 2282, dez. 2022. DOI: 10.1109/TEMC.2022.3201874. |
Abstract: | The electromagnetic interference (EMI) of overhead transmission lines (OHLs) to aboveground pipelines sharing the same right-of-ways has been a research topic for many years. Most studies focus on investigations of the induced currents and voltages at the mains frequency (50/60 Hz). However, significant voltage levels can also be induced, when the pipeline is subject to high-frequency excitation. The representation of earth conduction effects is very important to estimate accurately the level of the EMI. This article presents a detailed high-frequency analysis of OHL/pipeline configurations taking into consideration the frequency-dependent (FD) soil properties. Wise's earth formulation is adopted for the calculation of the earth return impedances and shunt admittances. Propagation characteristics, frequency-domain, and transient responses are calculated by using both the FD soil models and constant soil properties, as well as the classical transmission line approach of Carson. Frequency-domain responses calculated with Wise's formulation are compared against those obtained using the MoM-SO method of EMTP software. |
metadata.dc.description.unidade: | Faculdade de Tecnologia (FT) Departamento de Engenharia Elétrica (FT ENE) |
DOI: | 10.1109/TEMC.2022.3201874 |
metadata.dc.relation.publisherversion: | https://ieeexplore.ieee.org/document/9896805 |
Aparece en las colecciones: | Artigos publicados em periódicos e afins |
Los ítems de DSpace están protegidos por copyright, con todos los derechos reservados, a menos que se indique lo contrario.