Skip navigation
Use este identificador para citar ou linkar para este item: http://repositorio2.unb.br/jspui/handle/10482/48812
Arquivos associados a este item:
Não existem arquivos associados a este item.
Título: Influence of lossy ground on high-frequency induced voltages on aboveground pipelines by nearby overhead transmission lines
Autor(es): Britto, Amauri Gutierrez Martins
Papadopoulos, Theofilos A.
Datsios, Zacharias G.
Chrysochos, Andreas I.
Papagiannis, Grigoris K.
ORCID: https://orcid.org/0000-0002-2691-9061
https://orcid.org/0000-0002-8534-785X
https://orcid.org/0000-0002-5259-7043
https://orcid.org/0000-0002-5712-3859
https://orcid.org/0000-0002-9470-8573
Afiliação do autor: University of Brasília, Faculty of Technology, Department of Electrical Engineering LAPSE
University of Thrace, Power Systems Laboratory Department of Electrical and Computer Engineering Democritus, Xanthi, Greece
Aristotle University of Thessaloniki, High Voltage Laboratory School of Electrical & Computer Engineering, Thessaloniki, Greece
Cablel Hellenic Cables Group, Athens, Greece
School of Electrical and Computer Engineering, Aristotle University of Thessaloniki, Thessaloniki, Greece
Assunto: Interferência eletromagnética
Linhas de transmissão
Impedância
Condutividade elétrica
Data de publicação: 20-Set-2022
Editora: IEEE
Referência: BRITTO, Amauri Gutierrez Martins et al. Influence of lossy ground on high-frequency induced voltages on aboveground pipelines by nearby overhead transmission lines. IEEE Transactions on Electromagnetic Compatibility, [S. l.], v. 64, n. 6, 2273 - 2282, dez. 2022. DOI: 10.1109/TEMC.2022.3201874.
Abstract: The electromagnetic interference (EMI) of overhead transmission lines (OHLs) to aboveground pipelines sharing the same right-of-ways has been a research topic for many years. Most studies focus on investigations of the induced currents and voltages at the mains frequency (50/60 Hz). However, significant voltage levels can also be induced, when the pipeline is subject to high-frequency excitation. The representation of earth conduction effects is very important to estimate accurately the level of the EMI. This article presents a detailed high-frequency analysis of OHL/pipeline configurations taking into consideration the frequency-dependent (FD) soil properties. Wise's earth formulation is adopted for the calculation of the earth return impedances and shunt admittances. Propagation characteristics, frequency-domain, and transient responses are calculated by using both the FD soil models and constant soil properties, as well as the classical transmission line approach of Carson. Frequency-domain responses calculated with Wise's formulation are compared against those obtained using the MoM-SO method of EMTP software.
Unidade Acadêmica: Faculdade de Tecnologia (FT)
Departamento de Engenharia Elétrica (FT ENE)
DOI: 10.1109/TEMC.2022.3201874
Versão da editora: https://ieeexplore.ieee.org/document/9896805
Aparece nas coleções:Artigos publicados em periódicos e afins

Mostrar registro completo do item Visualizar estatísticas



Os itens no repositório estão protegidos por copyright, com todos os direitos reservados, salvo quando é indicado o contrário.