Skip navigation
Use este identificador para citar ou linkar para este item: http://repositorio.unb.br/handle/10482/41019
Arquivos associados a este item:
Não existem arquivos associados a este item.
Título: A wavelet-based restricted earth-fault power transformer differential protection
Autor(es): Aires, M. N. O.
Medeiros, R. P.
Costa, F. B.
Silva, Kleber Melo e
Chavez, J. J.
Popov, M.
Assunto: Proteção de transformadores
Aterramento elétrico
Transformada wavelet
Data de publicação: 2021
Editora: Elsevier
Referência: AIRES, M. N. O. et al. A wavelet-based restricted earth-fault power transformer differential protection. Electric Power Systems Research, v. 196, 107246, 2021. DOI: https://doi.org/10.1016/j.epsr.2021.107246.
Abstract: This paper proposes a restricted earth fault protection based on the wavelet transform (REFW) for detecting ground faults close to the transformer neutral point (turn-to-ground faults) and supporting the conventional phase differential protection, which presents limitations in this kind of faults. The proposed REFW protection uses only high-frequency components instead of phasor estimation, speeding up the detection of turn-to-ground faults. A performance comparison between the proposed wavelet-based restricted earth-fault differential protection and the respective conventional restricted earth-fault (REF) unit was accomplished considering simulated turn-to-ground faults, involving a few winding turns. The proposed method is more efficient and faster than the conventional one, reaching a success rate of 100%.
DOI: https://doi.org/10.1016/j.epsr.2021.107246
Versão da editora: https://www.sciencedirect.com/science/article/abs/pii/S0378779621002273
Aparece nas coleções:Artigos publicados em periódicos e afins

Mostrar registro completo do item Visualizar estatísticas



Os itens no repositório estão protegidos por copyright, com todos os direitos reservados, salvo quando é indicado o contrário.